Box-HT smoke exhaust cabinet fan according to EN 12101-3

The Box-HT line are destined to plants requiring the evacuation of fire smokes in environments like underground car parks, shopping malls, hospitals, schools, theatres, museums, etc.

This series is designed and manufactured according to the European directive EN 12101-3 obtaining the certification by an Autonomous Qualified Certification Institute. Box-HT are suitable to convey clean air and non dusty smokes up to the maximum temperature of 200°C in continuous service or in case of fire emergency at the temperature of 400°C for 120 minutes (F400).

For installation outside the fire compartment.

The line consists of 6 sizes with impeller from 250 mm to 500 mm.

  • Dismountable cabinet in galvanized steel sheet. Double inlet impeller with forward curved blades (sirocco) in galvanized steel sheet.
  • Belt coupling with self aligning supports, outside the airflow; height adjustable motor support plate for the tensioning of the belt; belt coupling is protected by a guard in galvanized sheet
  • Asynchronous three-phase motor, IP 55 mechanical protection, insulation class F, single or double polarity, suitable for S1 service, mounting type B3, construction according to IEC/EEC (UNEL MEC); arrangement 9; belt coupling with motor placed on the upper panel
  • Arrangement 12; belt coupling with motor placed aside on a common basement (only for motors above 7.5kW)

Read all

Features

  • Conveyed air: max 200°C in S1 service- 400°C for 120 min in S2 service (fire emergency)
  • Voltage and frequency: -three-phase (T) 400V-50 Hz